DLC02Detail DLC-02
Energy Valve

Energy Valve

A control valve with a built-in ultrasonic flow meter and supply-side temperature and pressure sensors that measures and manages cooling energy at each cabinet or CDU.

Family
Direct Liquid Cooling & Secondary Loop Support
Make
Taloar
Lead time
45 days
Projects
On request

How it works

The Taloar IDCV100C-S4 is a DN20 to DN50 tri-clamp valve (ISO 2852) for cold-plate liquid cooling. The valve sits on the return line and a temperature and pressure sensor on the supply line, so it measures flow, temperature difference, pressure, differential pressure and energy. It can hold a minimum temperature difference, applies a differential pressure function so every cabinet gets enough flow, and keeps its position or moves to a preset opening when the signal is lost. Settings are made over Bluetooth or remotely, and data goes out over Modbus RTU/TCP, MQTT or analog signals.

Role in the system

  1. 1.Flow control per cabinet with ±2% flow measurement
  2. 2.Temperature difference limiting for chiller-plant efficiency
  3. 3.Energy, flow, temperature and pressure data to the BMS or platform

Supplied to

Project references for this item are shared on request with your quotation.

Include in your quotation request

  • Valve size (DN20 / 25 / 32 / 40 / 50) and design flow
  • Signal (Modbus RTU/TCP, MQTT, 0(2)–10 V, 0(4)–20 mA)
  • Fluid (water, ethylene glycol, propylene glycol, deionized water)
  • Installation (integrated or split, primary or secondary side of the CDU)
  • 24 VDC isolated power supply
  • Quantity

This checklist is filled into the quotation form for you. Leave blank what you don't know yet.

Open the pre-filled quotation form